Construction T.O = open, vacuum varnished
|
|
Temperature class T40/B, on request insulation class F (155°C)
|
|
Protective class IP00 (for mounting in an appliance)
|
|
Phases 3
|
|
Frequency 48 Hz up to 400 Hz, other frequencies than 50 Hz lead to another power at the same type size
|
|
Safety standards VDE/SEV EN 61558
|
|
Safety standards UL/CSA on request UL/CSA materials or UL-approval
|
|
Resistance to short-circuiting conditionally short circuit protected with - temperature fuse - temperature switch - mini fuse in other case no resistance to short-circuiting
|
|
Bobbin DIN 41302, 1 or 2 chamber versions material: Polyamid 6 gf class B = 130°C with UL approval UL 94 HB
|
|
Insulants Polyester class B = 130°C with UL approval UL 94 V0
|
|
Copper wire Polyurethane mod. class F = 155°C with UL approval min. 0,04 mm, max. flat copper with ca. 500 qmm
|
|
Screening made of Cu-foil, reduces the max. power
|
|
Transformer core lamination conform DIN 41302 M530-50A, 0,5 mm thick (1,0 W/kg losses at 1,7 T) or M111-35N, 0,35 mm thick (1,1 W/kg losses at 1,5 T)
|
|
Terminals Free wires Stranded flexible wires Terminal connectors Plug pins Cable lugs
|
|
Mounting Base angle Distance bolts Holes in the core
|
|
Tappings possible
|
|