Datasheet as PDF Toroidal safety and isolating transformer to DIN EN 61558-2-4 and 2-6 with 5000 V 50 Hz test voltage pri - sec and a power of 15 VA up to 10000 VA at 400 Hz
|
|
|
|
Fields of application
|
|
Nets in ships and airplanes that are operated with 400 Hz (board nets).
|
|
Description
|
|
- low weight, weighs only half of a conventional transformer - without magnetic hum, low stray field - partly short-circuit-proof or not short-circuit-proof - reinforced insulation between primary and secondary - flat profile allows special design of appliances
|
|
Technical data
|
|
1AC-isolating- and safety-transformer voltage range primary 230 V or according to customers demand frequency: 400 Hz test voltage primary - secondary: 5000 V 50 Hz temperature class: B max. ambient temperature: 40°C fire class: UL94V0 transformer class: IP00 terminals: pri and sec free wires prepared for mounting with added mounting supply
|
|
Table
|
|
Secondary power
|
Dimensions in mm
|
Height without mounting material
|
Efficiency
|
No-load current
|
Voltage factor
|
Copper weight
|
Total weight
|
30 VA
|
Ø 36
|
H 25
|
84 %
|
6 mA
|
1,16
|
0,04 kg
|
0,08 kg
|
40 VA
|
Ø 40
|
H 30
|
88 %
|
8 mA
|
1,14
|
0,045 kg
|
0,10 kg
|
50 VA
|
Ø 45
|
H 25
|
88 %
|
8 mA
|
1,14
|
0,05 kg
|
0,17 kg
|
80 VA
|
Ø 50
|
H 30
|
90 %
|
10 mA
|
1,11
|
0,06 kg
|
0,20 kg
|
100 VA
|
Ø 56
|
H 26
|
91 %
|
10 mA
|
1,11
|
0,08 kg
|
0,28 kg
|
120 VA
|
Ø 56
|
H 26
|
92 %
|
11 mA
|
1,10
|
0,10 kg
|
0,30 kg
|
150 VA
|
Ø 60
|
H 30
|
93 %
|
12 mA
|
1,09
|
0,13 kg
|
0,35 kg
|
200 VA
|
Ø 70
|
H 30
|
94 %
|
15 mA
|
1,08
|
0,15 kg
|
0,40 kg
|
225 VA
|
Ø 75
|
H 30
|
94 %
|
16 mA
|
1,07
|
0,17 kg
|
0,50 kg
|
250 VA
|
Ø 76
|
H 30
|
94 %
|
17 mA
|
1,07
|
0,20 kg
|
0,54 kg
|
300 VA
|
Ø 80
|
H 35
|
94 %
|
18 mA
|
1,06
|
0,25 kg
|
0,07 kg
|
400 VA
|
Ø 93
|
H 35
|
95 %
|
20 mA
|
1,06
|
0,30 kg
|
0,90 kg
|
500 VA
|
Ø 95
|
H 40
|
96 %
|
25 mA
|
1,05
|
0,40 kg
|
1,00 kg
|
600 VA
|
Ø 98
|
H 50
|
96 %
|
28 mA
|
1,05
|
0,55 kg
|
1,30 kg
|
700 VA
|
Ø 98
|
H 55
|
96 %
|
30 mA
|
1,05
|
0,60 kg
|
1,60 kg
|
800 VA
|
Ø 110
|
H 50
|
97 %
|
32 mA
|
1,04
|
0,65 kg
|
2,00 kg
|
900 VA
|
Ø 115
|
H 50
|
97 %
|
40 mA
|
1,04
|
0,70 kg
|
2,10 kg
|
1000 VA
|
Ø 120
|
H 60
|
97 %
|
50 mA
|
1,04
|
0,95 kg
|
2,50 kg
|
1200 VA
|
Ø 120
|
H 65
|
97 %
|
60 mA
|
1,03
|
1,00 kg
|
2,80 kg
|
1500 VA
|
Ø 130
|
H 70
|
97 %
|
70 mA
|
1,03
|
1,30 kg
|
3,70 kg
|
2000 VA
|
Ø 140
|
H 80
|
97 %
|
80 mA
|
1,03
|
1,60 kg
|
4,80 kg
|
3000 VA
|
Ø 185
|
H 75
|
97 %
|
100 mA
|
1,03
|
2,65 kg
|
8,30 kg
|
5000 VA
|
Ø 210
|
H 100
|
97 %
|
300 mA
|
1,03
|
4,90 kg
|
14,0 kg
|
7500 VA
|
Ø 260
|
H 105
|
97 %
|
400 mA
|
1,03
|
7,20 kg
|
23,0 kg
|
10000 VA
|
Ø 325
|
H 110
|
98 %
|
450 mA
|
1,02
|
13,6 kg
|
39,0 kg
|
45000 VA / 400 Hz
|
Ø 410
|
H 370
|
-
|
-
|
-
|
-
|
200 kg
|
Technical changes and optimisation reserved. All details are guide values, variations are possible.
|
08/2013
|
Beispiel Breitbandtrafo
|
Sekundär- leistung
|
Abmessungen in mm
|
Höhenangabe ohne Befestigung
|
Frequenz
|
Leerlaufstrom
|
Kupfergewicht
|
Gesamtgewicht
|
BV
|
80 VA
|
Ø 100
|
50
|
30-25.000 Hz
|
7 mA
|
0,95 kg
|
1,6 kg
|
1567102
|
3000 VA
|
Ø 250
|
105
|
200-500 Hz
|
490 mA
|
3,5 kg
|
20,3 kg
|
14009015
|
3600 VA
|
Ø 215
|
100
|
1 kHz
|
110 mA
|
4,12 kg
|
12,0 kg
|
3469005
|
|
|
|
|