Toroidal transformers with rest hole potting


Datasheet as PDF
Open toroidal transformers (TRHT) with rest hole potting from 15 VA up to 10000 VA
Delivery with one or two screws or potted thread bolt or with through-hole with a sagging on the top and bottom side. Toroidal safety or insulation transformers.

ceenergyvdeEN61558-o-sm


Open toroidal transformers with rest hole pottingOpen toroidal transformers with rest hole pottingOpen toroidal transformers with rest hole potting

                     Thread depth: 8 mm                                      Standard: tapped hole
              other depths on demand


Table


Secondary
power

Dimensions

Height without
mounting

Efficiency

No-load
current

Voltage factor

Copper
weight

Total
weight

15 VA

59

H 29

80 %

6 mA

1,17

0,10 kg

0,33 kg

20 VA

60

H 30

82 %

6 mA

1,17

0,17 kg

0,44 kg

30 VA

74

H 30

84 %

6 mA

1,16

0,18 kg

0,53 kg

40 VA

76

H 35

88 %

8 mA

1,14

0,25 kg

0,69 kg

50 VA

79

H 37

88 %

8 mA

1,14

0,26 kg

0,73 kg

80 VA

90

H 38

90 %

10 mA

1,11

0,40 kg

1,01 kg

100 VA

92

H 43

93 %

10 mA

1,11

0,45 kg

1,25 kg

120 VA

95

H 46

92 %

11 mA

1,10

0,48 kg

1,35 kg

150 VA

96

H 50

93 %

12 mA

1,09

0,64 kg

1,64 kg

200 VA

115

H 50

94 %

15 mA

1,08

0,71 kg

2,04 kg

225 VA

116

H 52

94 %

16 mA

1,07

0,86 kg

2,23 kg

250 VA

117

H 60

94 %

17 mA

1,07

0,92 kg

2,57 kg

300 VA

125

H 62

94 %

18 mA

1,06

1,24 kg

2,97 kg

400 VA

132

H 61

95 %

20 mA

1,06

1,66 kg

3,73 kg

500 VA

142

H 71

96 %

25 mA

1,05

1,90 kg

4,23 kg

600 VA

140

H 80

96 %

28 mA

1,05

1,95 kg

4,84 kg

700 VA

145

H 86

96 %

30 mA

1,05

2,24 kg

4,95 kg

800 VA

173

H 70

97 %

32 mA

1,04

2,50 kg

6,20 kg

900 VA

173

H 78

97 %

40 mA

1,04

3,00 kg

7,00 kg

1000 VA

175

H 78

97 %

50 mA

1,04

3,50 kg

7,40 kg

1000 VA

200

H 70

97 %

50 mA

1,04

3,50 kg

9,60 kg

1200 VA

200

H 75

97 %

60 mA

1,03

4,40 kg

9,60 kg

1500 VA

210

H 84

97 %

70 mA

1,03

4,60 kg

10,5 kg

2000 VA

220

H 100

97 %

80 mA

1,03

7,50 kg

15,5 kg

2000 VA

200

H 110

97 %

80 mA

1,03

7,50 kg

16,9 kg

3000 VA

248

H 113

97 %

100 mA

1,03

10,0 kg

20,3 kg

4700 VA

272

H 100

97 %

300 mA

1,03

14,0 kg

28,0 kg

6800 VA

320

H 100

97 %

400 mA

1,03

20,0 kg

40,5 kg

10000 VA

350

H 150

98 %

450 mA

1,02

24,0 kg

72,0 kg

Technical changes and optimisation reserved. All details are guide values, variations are possible.
Other dimensions and technical changes on request.

02/2012


© 2016 Tauscher Transformatoren GmbH                                                                                                                                                         Impressum