Technical data toroidal transformersThis page in German

Construction

TRZT = open with covertape

TRHT = rest hole potting

TRWT = mounted on a metal angle

TRVTP = potted in a round housing - print version

TRVTF = potted in a round housing - free wire

TRVTE = potted in a rectangular housing - print version

TRVTU = potted in a round housing - print version

Temperature class

T40/B

on request insulation class F (155°C)

Protective class

IP00 (for mounting in an appliance)

Phases 

1 or 3

Frequency

48 Hz up to 400 Hz, at other frequencies than 50 Hz, the transformer will have another power at the same type size

VDE/SEV safety standards

open: EN 61558

potted: EN 61558

UL/CSA safety standards

on request UL/CSA materials or UL-approval

Test voltage

EN 61558-1-2/4: 5000 V pri -sec

Short circuit strength

partly short circuit proof with

- PTC

- temperature fuse

- temperature switch

- mini fuse

in other cases not short circuit proof

Core insulation and housing

Material:

Polyamid 6 class B = 130°C

with UL-approval UL 94 V2

Insulating tape

Polyester (Mylar) class B = 130°C

with UL-approval UL 94 V0

Copper wire

Polyimid mod. class H = 180°C

with UL-approval

Screen winding

Screen with copper tape, this reduces the max. power at the same type size

Transformer core lamination

conform to DIN 41302

M0H, 0,3 mm thick

(1,0 W/kg losses at1,7 T) orr

M111-35N, 0,35 mm thick 

(1,1 W/kg losses at 1,5 T)

Terminals

with pins (TRVTP / TRVTU)

with solder tags

with free wires

with stranded, flexible wires

with terminal connectors (TRWT)

with plug pins 2,8 - 4,8 - 6,3 mm

with cable eyes

Mounting

with a central screw, two washers and a metal disk or with a screw in the potted centre

Voltage

depends on the size

max: depends on the size

vacuum casting: 5000 V

Taps

possible

Current

max: 2000 A