Technical data of one-phase transformers
|
|
Type size
|
|
T.O = open, vacuum varnished
|
|
T.V = potted in a housing
|
|
Temperatureclass
|
|
T40/B
|
|
on request class F (155°C)
|
|
Protective class
|
|
IP00
|
|
Phases
|
|
1
|
|
Frequency
|
|
48 Hz up to 400 Hz
|
|
if there’s another frequency than 50 Hz, the transformer has another power at the same size
|
|
Standards VDE/SEV
|
|
open: EN 61558
|
|
potted: EN 61558
|
|
Standards UL/CSA
|
|
on request UL/CSA materials or UL-approval
|
|
Test voltage
|
|
EN 61558-1: 2500 V pri -sec
|
|
EN 61558-2-1/4: 4000 V pri -sec
|
|
Short-circuit strength
|
|
short-circuit proof up to 2,4 VA
|
|
partly short-circuit proof only with
|
|
- PTC
|
|
- temperature fuse
|
|
- temperature switch
|
|
- micro fuse
|
|
in other cases: not short-circuit proof
|
|
Bobbin
|
|
DIN 41302, 1 o. 2 chamber versions
|
|
Material:
|
|
Polyamid 6 gf class B = 130°C
|
|
with UL-approval UL 94 HB
|
|
Insulation material
|
|
Polyester class B = 130°C
|
|
with UL-approval UL 94 V0
|
|
Copper wire
|
|
Polyurethane mod. class F = 155°C
|
|
with UL-approval
|
|
min: 0,04 mm
|
|
max: flat copper with ca. 500 qmm
|
|
Screening
|
|
made of Cu-foil, decreases the max. power
|
|
Transformer core lamination
|
|
conform to DIN 41302
|
|
M530-50A, 0,5 mm thick
|
|
(2,3 W/kg losses at 1,0 T) or
|
|
M111-35N, 0,35 mm thick
|
|
(1,1 W/kg losses at 1,5 T)
|
|
Terminals
|
|
with solder lugs, above EI 48
|
|
free wires
|
|
stranded flexible wires
|
|
terminals, above Ei 60
|
|
flat plugs
|
|
plugs above EI 48
|
|
cable eyes
|
|
mounting on a printed circuit board
|
|
Mounting
|
|
base angle
|
|
distance bolts
|
|
holes in the core
|
|
mounting covers
|
|
Voltage
|
|
min: 0,1 V
|
|
max: depends on the size
|
|
for EI 78 and vacuum potting: 5000 V
|
|
Tappings
|
|
possible
|
|
Current
|
|
min: 0 A
|
|
max: depends on the size
|
|
for EI 150 approx. 500 A
|