three-phase toroidal-transformer potted 400VA until 30 kVA

cast-resin three-phase power-dry-transformers, cast-resin three-phase-isolation- transformers as toroidal core version

datasheet as PDF-File

VDE ISO 9001 certified

 

 

 

 

ernergy optimized

61558_onk

Ringkern-Transformator 500VA bis 10000 VA im Gehäuse, anklicken zum Vergrößern

applications

isolation transformer according to IEC/EN61558-2-4 for general purpose, e.g. for safe isolation for devices according to VDE0700/EN60335, or as a distribution transformer to build TN-netsystems. Useable for potential free net, for test systems or as power-ratio transformers. For machine controls,
vehicle construction, automotive techniques, as toroidal-isolating-transformer to supply medical rooms, as high current-transformer up to 10 kA.

description

The core of toroidal transformers consists of a thin grain-oriented tape, which is wound in direction of the magnetic flow corresponds with the direction of rolling and the losses are very low. The airgap just arises at the first and last winding, hence it is very small. Thus a low magnetic stray field, small weight and small volume are the results.

The three-phase toroidal transformer consists of three separate transformers without chain-linking to the core. The arrangement of the three phases can be selected. Thus an adjustment to difficult geometric relations is possible.

If one phase fails at the input, there will remain at least one phase without phase displacement at the output. In case an phase conductor has an earth fault, the voltages of the other two phase conductors remain constant, hence they won’t increase.

technical data

3AC-isolating transformer according IEC/EN61558-2-4,
 VDE 0570-2-4
fully casted in a housing
on request IP 54 possible
temperature class B
max. ambient temperature 40°C
fire class UL94 V0
prepared for protection index I
cable connectons
or block terminals touch safe according VBG4
or flat termination with bolt, not touch safe
frequency 50-60Hz
 

table

sec.-
power

efficiency

voltage-
factor

dimensions in mm

copper
weight

total
weight

BV

H

L

L1

B

B1

Ø

17 kVA

-

-

381

630

530

365

285

10,5

151 kg

-

2144001a

technical changes and optimization reserved

05/2008