toroidal transformer water- and dirt resistant in a housing - IP 65

safety and isolating transformers to DIN EN 61558-2-4 with 5000V / 50Hz test voltage pri - sec
and power 80VA to 520VA
IP65 according to IEC 529, VDE 0470 - higher dirt class according to IEC 60947 possible

datasheet as PDF-File

ce

symb_hydro

symb_pd_ip

61558_onk

61558_okf

61558_vnk

61558_vkf

symb-schutzisoliert

application

outdoor installation, industry environment, automotive environment,
environment with marked contamination layers,
tropical area, swimming- and sanitary technique

description

Transformer built in a housing IP 65.
The abbreviation IP means, according to DIN “international Protection but is used as “Ingres Protection” in the english-speaking area.
“6” means: dust infiltering will not be able (dust proof). Furthermore it is not possible to get ingress to dangerous parts with a wire.
“5” means: hose water-proof, jet of water from every direction towards the housing may not have any harmful effects.

drawing and table


hy_06_mm



type

sec.-
power

efficiency
η

noload-
current

voltagefactor
U0/UL

dimensions
in [ mm ]

copper-
weight

total-
weight

l

b

h

TRH.E

200 VA

94 %

15 mA

1,08

300

150

170

0,71 kg

4,0 kg

TRH.E

225 VA

94 %

16 mA

1,07

300

150

170

0,86 kg

4,3 kg

TRH.E

250 VA

94 %

17 mA

1,07

300

150

170

0,92 kg

4,2 kg

TRH.E

300 VA

94 %

18 mA

1,06

300

150

170

1,24 kg

4,6 kg

TRH.E

400 VA

95 %

20 mA

1,06

300

150

170

1,66 kg

5,4 kg

TRH.E

500 VA

96 %

25 mA

1,05

300

150

170

1,90 kg

5,9 kg

TRH.E

600 VA

96 %

28 mA

1,05

300

150

170

1,95 kg

6,5 kg

TRH.E

700 VA

96 %

30 mA

1,05

300

300

170

2,24 kg

6,6 kg

TRH.E

800 VA

97 %

32 mA

1,04

300

300

170

2,50 kg

7,9 kg

TRH.E

900 VA

97 %

40 mA

1,04

300

300

170

3,00 kg

8,7 kg

TRH.E

1000 VA

97 %

50 mA

1,04

300

300

170

3,50 kg

9,1 kg

TRH.E

1000 VA

97 %

50 mA

1,04

300

300

170

3,50 kg

11,2 kg

TRH.E

1200 VA

97 %

60 mA

1,03

300

300

170

4,40 kg

11,3 kg

TRH.E

1500 VA

97 %

70 mA

1,03

300

300

170

4,60 kg

12,2 kg

TRH.E

2000 VA

97 %

80 mA

1,03

300

300

170

7,50 kg

17,2 kg

TRH.E

2000 VA

97 %

80 mA

1,03

300

300

170

7,50 kg

18,6 kg

TRH.E

3000 VA

97 %

100 mA

1,03

300

300

170

10,0 kg

22,0 kg

TRH.E

4700 VA

97 %

300 mA

1,03

300

300

170

14,0 kg

29,7 kg

TRH.E

6800 VA

97 %

400 mA

1,03

600

600

170

20,0 kg

42,2 kg

technical changes and optimization reserved

 